EasyManua.ls Logo

Fujitsu GENERAL AUHG18LVLB - AOHG24 LBCB Compensation Rates

Fujitsu GENERAL AUHG18LVLB
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-2. Model: AOHG24LBCB
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
20 0.963 0.961 0.959
10 0.984 0.981 0.979 0.977 0.975
7.5 0.988 0.988 0.985 0.983 0.981 0.979
5 0.992 0.992 0.992 0.989 0.987 0.985 0.983
0 1.000 1.000 1.000 0.997 0.995 0.993 0.991
Indoor unit is lower than
outdoor unit *2
-5 1.000 1.000 1.000 0.997 0.995 0.993 0.991
-7.5 1.000 1.000 0.997 0.995 0.993 0.991
-10 1.000 0.997 0.995 0.993 0.991
-20 0.995 0.993 0.991
HEATING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
20 0.927 0.893 0.863
10 0.992 0.952 0.927 0.893 0.863
7.5 1.000 0.992 0.952 0.927 0.893 0.863
5 1.000 1.000 0.992 0.952 0.927 0.893 0.863
0 1.000 1.000 0.992 0.952 0.927 0.893 0.863
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.995 0.987 0.947 0.922 0.888 0.859
-7.5 0.993 0.984 0.945 0.920 0.886 0.857
-10 0.982 0.943 0.917 0.884 0.855
-20 0.908 0.875 0.846
- 49 -
6-2. Model: AOHG24LBCB 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18-24LBCB
OUTDOOR UNIT
AOHG18-24LBCB