En-8
2) Ceiling height
Select the setting values in the table below according to the
height of the ceiling.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
Standard (2.7m)
20
00
High ceiling (3.0m) 01
3) Outlet directions
Select the setting values in the table below for using a 3-way outlet.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
4-way
22
00
3-way 01
4) Static pressure
Select appropriate static pressure according to the installa-
tion conditions.
Please refer to the installation manual of each indoor unit for
details.
5) Cooler room temperature correction
Depending on the installed environment, the room tempera-
ture sensor may require a correction.
The settings may be selected as shown in the table below.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
Standard
30
00
Slightly Lower control 01
Lower control 02
Warmer control 03
6) Heater room temperature correction
Depending on the installed environment, the room tempera-
ture sensor may require a correction.
The settings may be changed as shown in the table below.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
7) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power fail-
ure etc.
Do not start and stop the indoor unit by this function in nor-
mal operation.
Be sure to operate by the control unit, or external input device.
8)
Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by
Wired remote controller temperature sensor.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit
temperature
sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit tempera-
ture sensor or remote controller unit sensor.
9) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote
controllers.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
A
44
00
B01
C02
D03
10) External input control
“Operation/Stop” mode or “Forced stop” mode can be elected.
(... Factory setting)
Setting Description
Function
Number
Setting
Value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02
9373328148-02_IM_EN_FR_SP.indb 89373328148-02_IM_EN_FR_SP.indb 8 9/14/2010 1:15:32 PM9/14/2010 1:15:32 PM

Other manuals for Fujitsu UTY-RNNUM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTY-RNNUM and is the answer not in the manual?

Fujitsu UTY-RNNUM Specifications

General IconGeneral
BrandFujitsu
ModelUTY-RNNUM
CategoryRemote Control
LanguageEnglish

Related product manuals