Fulton Boiler FBS Series
5 FBS 01/05
Specifications & Dimensions
Specifications
Model FB-S 1-1.0 1.5-1.0 2-1.0 3-1.0 4-1.0 4-1.25 6-1.25
Nominal steam output
T/h
1.0 1.5 2.0 3.0 4.0 4.0 6.0
Operating pressure
MPa
1.0 1.0 1.0 1.0 1.0 1.25 1.25
Operating steam temperature

184 184 184 184 184 194 194
Inlet water temperature

20 20
20
20
20
20
20
Water pump electric power (Kw) 2.2 2.2 2.2 3.0 3.0 4.0 5.5
Maximum fuel consumption
Light oil (Kg/h) 60.9 91.4 121.8 182.7 243.6 244.4 365.6
Heavy oil (Kg/h) 62.2 93.3 124.4 186.6 248.8 249.7 374
Natural gas (m
3
/h) 76.6 114.9 153.2 229.8 306.4 315.3 445
Town gas (m
3
/h) 189.4 284.1 378.8 568.2 757.6 778.7 1099.1
Note: 1) All steam output (kg/hr) ratings from 0 MPa at 100 , fuel consumption based on light oil 1,1200 Kcal/kg, heavy oil
10,960 kcal/kg, nature gas 8,900 kcal/m
3
, town gas 3600kcal/m
3
.
2) Specification and dimensions are approximate, the Fulton Companied reserve the right to change specifications or
dimensions.
Connection
Model FB-S 1-1.0 1.5-1.0 2-1.0 3-1.0 4-1.0 4-1.25 6-1.25
Main steam valve DN50 DN65 DN65 DN100 DN100
DN100 DN125
Safety valve DN40 DN40 DN40 DN50 DN50 DN50 DN80
Water inlet valve DN40 DN40 DN40
DN40
DN40
DN40
DN50
Drain valve DN40 DN40 DN40 DN50 DN50 DN50 DN50
Flue diameter (mm) 300 350 400 450 500 500 600
Water gauge outlet DN15 DN15
DN15
DN15
DN15
DN15
DN15
Note: 1) The connections of steam valve, safety valve and blow-down valve are all flange connections.
2) If the burners and /or pumps are different, the boiler electrical usages are also different, please based on the finally
drawings.