FC66002179 – Rev.00
12
Timing
Available only for Micronet panels installed directly on fan coil units, this function starts up the fan at regular
intervals (every 10 min.) and runs it at medium speed for 2 min. once the temperature inside the room has
reached the level set on the thermostat. It guarantees constant monitoring of the ambient air temperature; the
function is active only in summertime and only if enabled by the water temperature sensor.
A timed cycle is carried out also when the controller is powered (when started up for the first time or when the
power supply is restored after being interrupted).
Note
:
While the timing function is active, the thermostat and function selector will be disabled.
The timing function is available only for valveless units and only during summertime operation.
The timing function is not available for wall-mounted Micronet controllers.
On / off according to water temperature
According to the water temperature read by a specific sensor, the microprocessor will enable fan coil unit operation
according to the following logic:
Water temperature < 17°C: unit operation enabled in cooling mode
Water temperature 37°C: unit operation enabled in heating mode
For directions on how to install the water temperature sensor, see figures 13 to 17 in this manual.