FC66002179 – Rev.00
16
C7: four pipes
System characteristics
Number of pipes: 4
Valve: NO
Heating element: NO
List of functions activated in configuration 7:
• Room thermostat with control over air temperature:
• Local manual Cooling/Heating changeover
• On / off according to water temperature
• Timing (not available for wall-mounted Micronet controller):
Position of dipswitches for configuration 7:
1 2 3 4 5 6 7
Off Off Off Off Off Off On
On
Off
C13: two pipes, automatic changeover water side
System characteristics
Number of pipes: 2
Valve: NO
Heating element: NO
List of functions activated in configuration 13:
• Room thermostat with control over air temperature
• Automatic Cooling/Heating changeover according to water temperature
• Timing (not available for wall-mounted Micronet controller):
Position of dipswitches for configuration 13:
1 2 3 4 5 6 7
Off On On Off Off Off Off
On
Off