EasyManua.ls Logo

Gamatronic Centric 100 kVA - User Manual

Default Icon
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
GAMATRONIC ELECTRONIC INDUSTRIES LTD.
17 Hartom St., PO Box 45029, Jerusalem 91450, Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875
Email: info@gamatronic.co.il Website: www.gamatronic.com
2MUM-PPCN
U
U
P
P
S
S
S
S
Y
Y
S
S
T
T
E
E
M
M
Cat. no. 101SBD6x
U
U
s
s
e
e
r
r
G
G
u
u
i
i
d
d
e
e
f
f
o
o
r
r
m
m
o
o
d
d
e
e
l
l
s
s
5
5
0
0
k
k
V
V
A
A
-
-
2
2
0
0
0
0
k
k
V
V
A
A
Release 0.3, July 2013

Table of Contents

Other manuals for Gamatronic Centric 100 kVA

Questions and Answers

  • J
    Jessica WilliamsAug 17, 2025
    What to do if Gamatronic Centric 100 kVA batteries failed last test?
    • J
      jeremiah73Aug 17, 2025
      If the Gamatronic UPS batteries failed the last test, it could be because the battery voltage was lower than acceptable. You can check the voltage threshold value for the battery test (350 V is recommended) and repeat the test after 2 hours. Also, check the DC voltage between the leads of each battery; if any battery measures less than 10 V, replace it immediately.
  • K
    kimberlyfloydAug 19, 2025
    Why are all Gamatronic Centric 100 kVA modules not responding?
    • L
      laurie51Aug 19, 2025
      If all Gamatronic UPS modules are not responding, there may be a communication problem between the modules and the controller. Check for breaks or disconnections in the communication cable. You might also need to reboot the controller. A defective module could be monopolizing the communication channel; try removing one module at a time to see if the problem is resolved, replacing any defective module.
  • X
    xramirezAug 22, 2025
    What to do if actual responding modules are less than defined on Gamatronic UPS?
    • K
      kevinbraunAug 22, 2025
      If the actual responding modules are less than defined on your Gamatronic UPS, it means either too many modules were defined to the system or too few modules were inserted. If too many modules were defined, correct the definition in Setup > System > Number of modules. If too few modules were inserted, insert the proper number of modules.
  • R
    Rodney WrightAug 25, 2025
    How to fix AC input failure on Gamatronic Centric 100 kVA UPS?
    • H
      Hailey RiveraAug 26, 2025
      If there is an AC input failure on your Gamatronic UPS, verify that the input circuit breakers are ON and that the input cable connections are secure, because there is no AC input voltage.
  • C
    Cameron LarsonAug 27, 2025
    What happens if AC input voltage is high on Gamatronic Centric 100 kVA UPS?
    • J
      Jason RomanAug 28, 2025
      If the AC input voltage is too high on your Gamatronic UPS, the UPS can handle it for a short time before transferring the load to bypass. If the bypass voltage is also too high, the UPS will switch to battery mode, because the AC input voltage is higher than normal.
  • V
    Veronica StoneAug 30, 2025
    What happens if AC input voltage is low on Gamatronic Centric 100 kVA UPS?
    • P
      Patrick JohnsonAug 31, 2025
      If the AC input voltage is too low on your Gamatronic UPS, the UPS automatically transfers the load to bypass. If the bypass voltage is also too low, the UPS will go to battery mode, because the input voltage is lower than normal.
  • M
    michellefreySep 2, 2025
    How to fix adapter PC710 not responding in Gamatronic Centric 100 kVA?
    • A
      Angela WellsSep 2, 2025
      Replace PC710, because PC710 is a communication adapter in the computer rack.
  • C
    calvin55Sep 5, 2025
    What does a temperature fault mean on my Gamatronic Centric 100 kVA?
    • J
      Jennifer SmithSep 5, 2025
      If the Gamatronic UPS temperature fault occurs, it means the battery temperature sensor has registered a temperature outside of the acceptable range (too high or too low). You can display the measured temperature via the Status screen by tapping on the battery icon.
  • J
    Julie RuizSep 8, 2025
    What does it mean when the Emergency Power Off is active on my Gamatronic Centric 100 kVA?
    • L
      Laura LopezSep 8, 2025
      If the Gamatronic UPS shows that the Emergency Power Off is active, it means the EPO switch has been activated.
  • M
    Michael CarpenterSep 10, 2025
    Why is the static switch sending an alarm on my Gamatronic UPS?
    • L
      Lauren VargasSep 12, 2025
      If the static switch on your Gamatronic UPS is sending an alarm or warning and one of the voltage measurements for the inverter, bypass, or output phases is shown as 0, it may indicate that one of the AC fuses on the front of the left column has burned out.

Gamatronic Centric 100 kVA Specifications

General IconGeneral
Apparent Power100 kVA
TopologyDouble Conversion Online
Input Frequency50/60 Hz
Output Frequency50/60 Hz
Battery TypeValve Regulated Lead Acid (VRLA)
Communication InterfaceRS232, USB, SNMP
Operating Temperature0°C to 40°C
Humidity0% to 95% (non-condensing)