FEATURE INFORMATION
6-3
(4.0) Event Print Format
Since there is a large variety of printers and it is
impossible to interface with all of them, the 565 feeder relays
are standardized to interface with EPSON FX-80 printers
with serial input or other compatible printer. See section 2 of
this manual for additional details.
The format of the event printout is specified as follows:
a)page size of 8.5"×11".
b)a header line is printed at the top of each page, on
which the column fields are specified; they are:
- event reference number
- cause of event
- date and time
- any applicable measured parameters at the time of
event (ie. 4 currents and 3 voltages)
c)each event takes two lines (because both cause of
event and time/date fields require two lines).
For event printing, the header line is printed at the top
of each page.
The following is an example of event printout:
No. Cause of Event Time/Date Ia Ib Ic Ig Vax Vbx Vcx
(A) (A) (A) (A) (KV) (KV) (KV)
01 Phase A Timed 16:42:56 1800 400 400 0 2.3 4.6 4.6
O/C Trip 03/15/92
02 System Manual 16:06:35
Reset 03/15/92
03 Undervolt Alarm 09:57:43 400 400 400 0 4.6 4.6 4.6
Reset 03/15/92
04 Undervoltage 09:53:09 400 400 400 0 4.2 4.6 4.6
Alarm 03/15/92
05 Analog Input 09:49:32
Alarm Reset 03/15/92
06 Analog Input 21:02:16
Alarm 03/14/92