SETPOINTS MODE
5-6
Gnd Inst Trip 2 Level 3.0 × P/U 1 to 8 0.1
Gnd Inst Trip Delay Inst. 0 (Inst.) to 40 cycles 1 cycle
Gnd Inst Trip Relay Trip. Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
Gnd HISET Inst Trips Enabled. Enabled/Disabled
Gnd HISET Inst Trip 3.0 × P/U 1 to 7 0.5
Gnd HISET Inst Delay Inst. 0 (Inst.) to 40 cycles 1 cycle
Gnd HISET Inst Relay Trip&Aux1 Trip, Trip&Aux1, Aux2
Gnd Autoblock Inst HISET Disabled. Enabled/Disabled
Gnd Autoblock HISET After Recl. #4. 1 to 4 1
Gnd LOSET Inst Trips Enabled. Enabled/Disabled
Gnd LOSET Inst Trip 2.0 × P/U 1 to 7.0 0.5
Gnd LOSET Inst Delay Inst. 0 (Inst.) to 40 cycles 1 cycle
Gnd LOSET Inst Relay Trip&Aux1. Trip, Trip&Aux1, Aux2
Gnd Autoblock Inst LOSET Disabled. Enabled/Disabled
Gnd Autoblock LOSET After Recl. #4. 1 to 4 1
Trip Time (Sec) × P/U 1.0 0.1 to 1092.2 sec 0.1 sec
4. Configuration setpoints.
Set Time Current time. (hh:mm:ss) 00:00:00 to 23:59:59 1 sec.
Set Date Current date. (mm/dd/yy) Jan 01, 1969 to Dec 31, 2068 1 day
Switch Contact Function.
Reset Blocked Disabled. Disabled, SW1 to SW8
Block Inst Trips Disabled. Disabled, SW1 to SW8
Block Timed O/C Trips Disabled. Disabled, SW1 to SW8
Block Gnd Trips Disabled. Disabled, SW1 to SW8
Definite Time #1 Alarm Disabled. Disabled, SW1 to SW8
Definite Time #1 Delay 1 Sec. 1 to 255 sec 1 sec
Definite Time #1 Relay Aux2. Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Definite Time #2 Alarm Disabled. Disabled, SW1 to SW8
Definite Time #2 Delay 1 Sec. 1 to 255 sec 1 sec
Definite Time #2 Relay Aux2. Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
External Trip #1 Disabled. Disabled, SW1 to SW8
External Trip #1 Relay Trip & Aux1. Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
External Trip #1 Delay 0 cyc. 0 (Inst.) to 60 cycles 1 cyc
External Trip #2 Disabled. Disabled, SW1 to SW8
External Trip #2 Relay Trip & Aux1. Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
External Trip #2 Delay 0 cyc. 0 (Inst.) to 60 cycles 1 cyc
External Trip #3 Disabled. Disabled, SW1 to SW8
External Trip #3 Relay Trip & Aux1. Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
External Trip #3 Delay 0 cyc. 0 (Inst.) to 60 cycles 1 cyc
External Trip #4 Disabled. Disabled, SW1 to SW8
External Trip #4 Relay Trip & Aux1. Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&Aux2
External Trip #4 Delay 0 cyc. 0 (Inst.) to 60 cycles 1 cyc
Curve Adjustment Disabled. Disabled, SW1 to SW8
External Reset Disabled. Disabled, SW1 to SW8
External Trip Disabled. (575) Disabled, SW1 to SW8
External Trip Relay Trip&Aux1. (575) Trip, Trip&Aux1, Aux2
External Trip Delay Inst. (575) 0 (Inst.) to 60 cycles 1 cycle
Reclosable Trip Disabled. (575) Disabled, SW1 to SW8
Setpoint Name Factory Setpoint Range Step
(575)
U
|
|
|
V
|
|
|
W
(565)
U
|
V
|
W