SETPOINTS MODE
5-7
Reclosable Trip Relay Trip&Aux1. Trip, Trip&Aux1, Aux2
Programmable Trip Disabled. Disabled, SW1 to SW8
Programmable Trip Relay Trip&Aux1. Trip, Trip&Aux1, Aux2
Programmable Trip Type Non-Recls. Recls/Non-Recls
Curve Adjustment Disabled. Disabled, SW1 to SW8
Alternative Phase Curve Disabled. Disabled, SW1 to SW8
Alternative Ground Curve Disabled. Disabled, SW1 to SW8
Auto-Reclosure Block Disabled. Disabled, SW1 to SW8
External Reset Disabled. Disabled, SW1 to SW8
Switch Contact Configuration.
SW1 Contact Normally Open (inactive). Open/Closed
SW2 Contact Normally Open (inactive). Open/Closed
SW3 Contact Normally Open (inactive). Open/Closed
SW4 Contact Normally Open (inactive). Open/Closed
SW5 Contact Normally Open (inactive). Open/Closed
SW6 Contact Normally Open (inactive). Open/Closed
SW7 Contact Normally Open (inactive). Open/Closed
SW8 Contact Normally Open (inactive). Open/Closed
Output Relay Operation.
Trip Relay Pulsed. (565) Latched/Pulsed
Trip Relay Pulse Time 0.6 Sec. (565) 0.1 to 0.6 sec 0.1 sec
Aux1 Relay Unlatched. (Pulsed for 575) Latched, Unlatched, and Pulsed
Aux1 Relay Pulse Time 0.6 Sec. (0.1 Sec. for 575) 0.1 to 0.6 sec 0.1 sec
Aux2 Relay Unlatched. Latched, Unlatched, and Pulsed
Aux2 Relay Pulse Time 0.6 Sec. 0.1 to 0.6 sec 0.1 sec
575 Features.
Breaker Response Delay 1ms. 1 to 167ms 1ms
Breaker Discrep. Disabled. (565) Enabled/Disabled
Breaker Discrep. Delay 1000mS. 100 to 1000mS 10mS
Trip Coil Supervision Disabled. Enabled/Disabled
Accumulated KA Alarm Disabled. Enabled/Disabled
Accumulated KA Alarm 5000. 5000 to 100,000KA 10KA
KA Alarm Relay Aux1. (Aux2 for 575) Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Event Recording Enabled. Enabled/Disabled
Event Printing Offline. Online/Offline
Cold Load P/U Block Lowset. (575) Lowset, Highset, Both
Cold Load P/U Delay 0.0 Sec. 0 to 10 sec 0.1 sec
MTM Comm Enabled. Enabled/Disabled
5. Analog Input setpoints.
Analog Input Disabled. Enabled/Disabled
Edit Analog Input Title? No. Yes/No
Edit Analog Input Units? No. Yes/No
Min Curr Scale Value 4.00. 0 to 1023 0.01
Max Curr Scale Value 20.00. 0 to 1023 0.01
Analog Input Trip Disabled. Enabled/Disabled
Analog In Trip 16.00. Min Curr Scale Value to Max Curr Scale Value
Analog In Trip Delay 1 Sec. 1 to 255 sec 1 sec
Analog In Trip Relay Trip. (Trip&Aux1 for 575) Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2
Analog Input Alarm Disabled. Enabled/Disabled
Setpoint Name Factory Setpoint Range Step
U
V
W
(575)