SETPOINTS MODE
5-9
Location Message Line Description
Amp Demand Alarm Relay Aux1. (Aux2 for 575) Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
KW Demand Enabled. Enabled/Disabled
KW Demand Time Period 5 Min. 5 to 120 Min 1 Min
KW Demand Alarm Disabled. Enabled/Disabled
KW Demand Alarm Level 1000 kW. 100 to 65,000 kW 100 kW
KW Demand Alarm Relay Aux1. (Aux2 for 575) Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
KVAR Demand Enabled. Enabled/Disabled
KVAR Demand Time Period 5 Min. 5 to 120 Min 1 Min
KVAR Demand Alarm Disabled. Enabled/Disabled
KVAR Demand Al’m Level 1000 kVAR. 100 to 65,000 kVAR 100 kVAR
KVAR Demand Al’m Relay Aux1. (Aux2 for 575) Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
11. MTM Metering setpoints.
MTM Comm. Alarm Disabled. Enabled/Disabled
MTM Comm. Alarm Relay Aux2. Aux1, Aux2, Aux1&2
MTM CT Select Common. Common/Separate
MTM CT Rating Primary 100 A. 5 to 5000 A 5 A
Power Factor Alarm Disabled. Enabled/Disabled
P/F Leading Alarm Level 0.75. 0 to 1 0.05
P/F Lagging Alarm Level 0.75. 0 to 1 0.05
P/F Alarm Delay 5.0 Sec. 1 to 127 sec 0.5 sec
P/F Alarm Relay Aux1. (Aux2 for 575) Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Power Factor Trip Disabled. Enabled/Disabled
P/F Leading Trip Level 0.70. 0 to 1 0.05
P/F Lagging Trip Level 0.70. 0 to 1 0.05
P/F Trip Delay 1.0 Sec. 1 to 127 sec 0.5 sec
P/F Trip Relay Aux1. (Trip&Aux1 for 575) Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Frequency Alarm Disabled. Enabled/Disabled
Under Freq. Alarm Level 58.0 Hz. 40 to 60 Hz 0.1 Hz
Over Freq. Alarm Level 62.0 Hz. 50 to 72 Hz 0.1 Hz
Frequency Alarm Delay 5.0 Sec. 1 to 127 sec 0.5 sec
Frequency Alarm Relay Aux1. (Aux2 for 575) Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
Frequency Trip Disabled. Enabled/Disabled
Under Freq. Trip Level 56.0 Hz. 40 to 60 Hz 0.1 Hz
Over Freq. Trip Level 64.0 Hz. 50 to 72 Hz 0.1 Hz
Frequency Trip Delay 1.0 Sec. 1 to 127 sec 0.5 sec
Frequency Trip Relay Aux1. (Trip&Aux1 for 575) Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
MTM Scaling Factor 655. 1 to 655 1
Voltage Reversal Trip Disabled. Enabled/Disabled
Voltage Reversal Delay 1.0 sec. 1 to 127 sec. 0.5 sec
Voltage Reversal Relay Trip Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&Aux2,
Trip&Aux1&Aux2 (575: Trip, Trip&Aux1, Aux2)
12. Auto Reclosure setpoints. (575 only)
Auto Reclosure Disabled. Enabled/Disabled
No. Of Reclose Shots 4. 0 to 4 1
Shot 1 Dead Time 2.0 sec. 0.3 to 300 sec. 0.1 sec.
Shot 2 Dead Time 4.0 sec. 0.3 to 300 sec. 0.1 sec.
Shot 3 Dead Time 6.0 sec. 0.3 to 300 sec. 0.1 sec.
Shot 4 Dead Time 8.0 sec. 0.3 to 300 sec. 0.1 sec.
Scheme Reset TIme 5.0 sec. 1 to 255 sec. 1 sec.
Reclosure Enable Relay Aux2. None, Aux1, Aux2, Aux1&2
13. Phase Curves setpoints. (575 only)