EasyManua.ls Logo

GE Multilin MM200 - Power Supply and Communications Specs

GE Multilin MM200
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22 MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
SPECIFICATIONS QUICKSTART GUIDE
THERMISTOR INPUTS
Sensor type:........................................................... Positive temperature coefficient PTC (R
HOT
= 100 to
30000 ohms), negative temperature coefficient NTC (R
HOT
=
100 to 30000 ohms)
Accuracy:................................................................±6% of reading or ±100 ohms, whichever is greater
1.5.3 Outputs specifications
OUTPUT RELAYS
Configuration: ...................................................... electromechanical 2 x Form-A and 1 x Form-C
Contact material:................................................ silver-alloy
Operate time:........................................................10 ms
Minimum contact load:.................................... 10 mA at 5 V DC
Maximum switching rate:...............................300 operations per minute (no load), 30 operations per
minute (load)
Mechanical life:....................................................10 000 000 operations
Continuous current:...........................................5 A at 60°C
Make and carry for 0.2s:..................................30 A per ANSI C37.90 (not UL rated)
OUTPUT RELAY BREAK CAPACITY (FORM-A RELAY)
AC resistive, 120 V AC: ......................................5 A
AC resistive, 250 V AC: ......................................5 A
AC inductive, PF = 0.4:.......................................240 VA pilot duty
DC resistive, 30 V DC:........................................5 A
OUTPUT RELAY BREAK CAPACITY (FORM-C RELAY)
AC resistive, 120 V AC: ......................................5 A normally-open, 5 A normally-closed
AC resistive, 240 V AC: ......................................5 A normally-open, 5 A normally-closed
AC inductive, PF = 0.4:.......................................240 VA pilot duty
DC resistive, 30 V DC:........................................5 A
1.5.4 Power supply specifications
POWER SUPPLY (LO RANGE)
Nominal:..................................................................24 V DC
Range:......................................................................18 to 36 V DC
Power Consumption:.........................................10 W typical
POWER SUPPLY (HI RANGE)
Nominal:..................................................................120 to 240 V AC; 125 to 250 V DC
Range:......................................................................60 to 300 V AC (50 and 60 Hz); 84 to 250 V DC
Power consumption: .........................................10 W typical
Voltage withstand:.............................................2 × highest nominal voltage for 10 ms
1.5.5 Communications specifications
DEVICENET (COPPER)
Modes: .....................................................................slave (125, 250, and 500 kbps)
Connector: .............................................................5-pin terminal
PROFIBUS (COPPER)
Modes: .....................................................................DP V0 slave, up to 1.5 Mbps
Connector: .............................................................5-pin terminal
RS485 PORT
Port:........................................................................... opto-isolated
Baud rates: ............................................................up to 115 kbps
Protocol:..................................................................Modbus RTU, half-duplex
Maximum distance:...........................................1200 m
Isolation: .................................................................2 kV

Other manuals for GE Multilin MM200