EasyManua.ls Logo

GE Multilin MM200 - Testing, Physical, and Environmental Specs

GE Multilin MM200
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
QUICKSTART GUIDE SPECIFICATIONS
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 23
1.5.6 Testing and certification
CERTIFICATION
ISO:.............................................................................Manufactured under an ISO9001 registered program
CE: ..............................................................................Conforms to EN 60255-26 (EN 50263), EN 55022/CISPR22/
EN 61000-6-2, EN 60255-27
cULus:.......................................................................Conforms to UL 508 / UL 1053 and C22.2.14-05 (CSA)
TYPE TESTS (* TEST NOT PERFORMED FOR AC PSU)
Relative Humidity Cyclic:.................................IEC 60068-2-30: 55°C at 95% RH
Hot: ............................................................................IEC 60068-2-2 (Hot Start) 16 hours
Cold: ..........................................................................IEC 60068-2-1 (Cold Start) 16 hours
Dielectric Strength:.............................................IEC 60255-5: 2000 V AC
Insulation Resistance:.......................................IEC 60255-5: >100 MΩ / 500 V DC / 10 s
Impulse Voltage:..................................................IEC 60255-5: 5kV
Sinusoidal Vibration:..........................................IEC 60255-21-1: 2 g
Shock and Bump:................................................IEC 60255-21-2: 5 g / 10 g / 15 g
Seismic*:..................................................................IEC 60255-21-3: 2 g
Damped Oscillatory Burst:..............................IEC 60255-22-1: 1 MHz 2.5 kV / 1 kV
Electrostatic Discharge Immunity - Air
and Direct:.........................................................IEC 60255-22-2: 15 kV / 8 kV
Radiated RF Immunity:.....................................IEC 60255-22-3: 10 V/m
Electrical Fast Transient / Burst
Immunity: ..........................................................IEC 60255-22-4: 4 kV
Surge Immunity:..................................................IEC 60255-22-5: 2 kV / 1 kV
Conducted RF Immunity:.................................IEC 60255-22-6: 150 kHz to 80 MHz 10 V/m rms
Radiated RF Emission: ......................................IEC 60255-25: Group 1 Class A
Conducted RF Emission: ..................................IEC 60255-25: Group 1 Class A
Ingress of Solid Objects and Water:...........IEC 60529: IP54 (front), IP20 (back)
Power Frequency Magnetic Field
Immunity*: ........................................................IEC 61000-4-8: 100 A/m cont; 1000 A/m 1 to 3 seconds
Pulse Magnetic Field Immunity*:.................IEC 61000-4-9: 1000 A/m
Damped Oscillatory Magnetic Field
Immunity*: ........................................................IEC 61000-4-10: 100 A/m
Voltage Dip; Voltage Interruption:...............IEC 60255-11: 5 msec interruption
Fast Transient SWC*:.........................................IEEE C37.90.1: ±4 kV
Oscillatory Transient SWC*:...........................IEEE C37.90.1: ±2.5 kV
Radiated / Conducted Emissions:...............EN55022: Class A
Power frequency immunity test*: ...............IEC 60255-22-7: Class A
1.5.7 Physical specifications
DIMENSIONS
Size: ...........................................................................Base: 78 mm (W) × 90 mm (H) × 113 mm (D) [+ terminals
10mm]
BCP: 75 mm (W) × 75 mm (H) × 31 mm (D)
Weight (Base):.......................................................0.5 kg

Other manuals for GE Multilin MM200