Quick Start Guide
Commonly Used Tools
- Phillips Head Screwdriver
- Flat Head Screwdriver
- Hammer
- Wire Cutter/Stripper
WARNING
• Recommended installation by licensed electrician.
• High Voltage (There may be more that one source of supply)
disconnect all power sources before servicing.
• Risk of electric shock – All terminals are live.
• Use copper wire only.
• Close the cover after setting.
• Tighten connections to 25 lbf-in.
• Use correct gauge wire (8-14 AWG) based on local electrical code
of at least 105C rating.
• Approved for outdoor use.
• Wire strip length ½”
• GROUNDING: National Electrical Code requires that grounding must be
continuous and in proper electrical contact in all grounding conductors,
metallic conduits and grounding terminals.
MIN. COPPER WIRE
SIZE (AWG)
MAX LOAD
(AMP)
MINIMUM INSULATION
TEMP (°C)
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
14 15 60
12 20 60
10 30 60
8 40 105
USE CORRECT GAUGE WIRE PER LOCAL ELECTRICAL CODE