489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE 39
2B5E Mvar Demand Minimum 0 to 200 1 × Rated F3 0
2B5F Mvar Demand Maximum 0 to 200 1 × Rated F3 125
2B60 MW Demand Minimum 0 to 200 1 × Rated F3 0
2B61 MW Demand Maximum 0 to 200 1 × Rated F3 125
2B62 MVA Demand Minimum 0 to 200 1 × Rated F3 0
2B63 MVA Demand Maximum 0 to 200 1 × Rated F3 125
ANALOG INPUT/OUTPUT / ANALOG INPUT 1
2C00 Analog Input 1 0 to 3 1 F129 0
2C05 Analog Input 1 Units 0 to 6 1 F22 _
2C08 Analog Input 1 Minimum –50000 to 50000 1 Units F12 0
2C0A Analog Input 1 Maximum –50000 to 50000 1 Units F12 100
2C0C Block Analog Input 1 From Online 0 to 5000 1 s F1 0
2C0D Analog Input 1 Alarm 0 to 2 1 F115 0
2C0E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2C0F Analog Input 1 Alarm Level –50000 to 50000 1 Units F12 10
2C11 Analog Input 1 Alarm Pickup 0 to 1 1 F130 0
2C12 Analog Input 1 Alarm Delay 1 to 3000 1 s F2 1
2C13 Analog Input 1 Alarm Events 0 to 1 1 F105 0
2C14 Analog Input 1 Trip 0 to 2 1 F115 0
2C15 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2C16 Analog Input 1 Trip Level –50000 to 50000 1 Units F12 20
2C18 Analog Input 1 Trip Pickup 0 to 1 1 F130 0
2C19 Analog Input 1 Trip Delay 1 to 3000 1 s F2 1
2C1A Analog Input 1 Name 0 to 12 1 F22 _
ANALOG INPUT/OUTPUT / ANALOG INPUT 2
2C40 Analog Input 2 0 to 3 1 F129 0
2C45 Analog Input 2 Units 0 to 6 1 F22 _
2C48 Analog Input 2 Minimum –50000 to 50000 1 Units F12 0
2C4A Analog Input 2 Maximum –50000 to 50000 1 Units F12 100
2C4C Block Analog Input 2 From Online 0 to 5000 1 s F1 0
2C4D Analog Input 2 Alarm 0 to 2 1 F115 0
2C4E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2C4F Analog Input 2 Alarm Level –50000 to 50000 1 Units F12 10
2C51 Analog Input 2 Alarm Pickup 0 to 1 1 F130 0
2C52 Analog Input 2 Alarm Delay 1 to 3000 1 s F2 1
2C53 Analog Input 2 Alarm Events 0 to 1 1 F105 0
2C54 Analog Input 2 Trip 0 to 2 1 F115 0
2C55 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2C56 Analog Input 2 Trip Level –50000 to 50000 1 Units F12 20
2C58 Analog Input 2 Trip Pickup 0 to 1 1 F130 0
2C59 Analog Input 2 Trip Delay 1 to 3000 1 s F2 1
2C5A Analog Input 2 Name 0 to 12 1 F22 _
ANALOG INPUT/OUTPUT / ANALOG INPUT 3
2C80 Analog Input 3 0 to 3 1 F129 0
2C85 Analog Input 3 Units 0 to 6 1 F22 _
2C88 Analog Input 3 Minimum –50000 to 50000 1 Units F12 0
2C8A Analog Input 3 Maximum –50000 to 50000 1 Units F12 100
2C8C Block Analog Input 3 From Online 0 to 5000 1 s F1 0
2C8D Analog Input 3 Alarm 0 to 2 1 F115 0
2C8E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2C8F Analog Input 3 Alarm Level –50000 to 50000 1 Units F12 10
2C91 Analog Input 3 Alarm Pickup 0 to 1 1 F130 0
2C92 Analog Input 3 Alarm Delay 1 to 3000 1 s F2 1
Table CG–1: 489 Memory Map (Sheet 27 of 30)
ADDR Name RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page page 42