6-13 Terminal 53 High Current
0.01 - 20.00 mA * 20.00 mA
6-14 Term. 53 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
6-15 Term. 53 High Ref./Feedb. Value
-4999 - 4999 * 50.000
6-16 Terminal 53 Filter Time Constant
0.01 - 10.00 s * 0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2X Analog Input 2
6-22 Terminal 60 Low Current
0.00 - 19.99 mA * 0.14 mA
6-23 Terminal 60 High Current
0.01 - 20.00 mA * 20.00 mA
6-24 Term. 60 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
6-25 Term. 60 High Ref./Feedb. Value
-4999 - 4999 * 50.00
6-26 Terminal 60 Filter Time Constant
0.01 - 10.00 s * 0.01 s
6-8X Keypad potentiometer
6-81 Keypad potm. Low Reference
-4999 - 4999 * 0.000
6-82 Keypad potm. High Reference
-4999 - 4999 * 50.00
6-9X Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] Logic Controller Digital Output A
6-93 Terminal 42 Output Min Scale
0.00 - 200.0 % * 0.00 %
6-94 Terminal 42 Output Max Scale
0.00 - 200.0 % * 100.0 %
7-XX Controllers
7-2X Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3X Process PI
Ctrl. 7-30 Process PI Normal/ Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0 - 200.0 Hz * 0.0 Hz
7-33 Process PI Proportional Gain
0.00 - 10.00 * 0.01
7-34 Process PI Integral Time
0.10 - 9999 s * 9999 s
7-38 Process PI Feed Forward Factor
0 - 400 % * 0 %
7-39 On Reference Bandwidth
0 - 200 % * 5 %
8-XX Comm. and Options
8-0X General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] GE Drive RS485
8-03 Control Word Timeout Time
0.1 - 6500 s * 1.0 s
8-04 Control Word Timeout Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3X GE Drive Port Settings
8-30 Protocol
*[0] GE Drive
[2] Modbus RTU
8-31 Address
1 - 247 * 1
8-32 GE Drive Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
8-33 GE Drive Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 * 0.010 s
8-36 Max Response Delay
0.100 - 10.00 s * 5.000 s
8-5X Digital/Bus
8-50 Coasting Select
[0] DigitalInput
[1] Bus
[2] LogicAnd
*[3] LogicOr
8-51 Quick Stop Select
See par. 8-50 * [3] LogicOr
8-52 DC Brake Select
See par. 8-50 * [3] LogicOr
8-53 Start Select
See par. 8-50 * [3] LogicOr
8-54 Reversing Select
See par. 8-50 * [3] LogicOr
8-55 Set-up Select
See par. 8-50 * [3] LogicOr
8-56 Preset Reference Select
See par. 8-50 * [3] LogicOr
8-9X Bus Jog / Feedback
8-94 Bus feedback 1
0x8000 - 0x7FFF * 0
13-XX Controller Logic
13-0X Logic Controller Settings
13-00 Logic Controller Mode
*[0] Off
[1] On
13-01 Start Event
[0] False
[1] True
[2] Running
[3] InRange
[4] OnReference
[7] OutOfCurrentRange
[8] BelowILow
[9] AboveIHigh
[16] ThermalWarning
[17] MainOutOfRange
[18] Reversing
[19] Warning
[20] Alarm_Trip
[21] Alarm_TripLock
[22-25] Comparator 0-3
[26-29] LogicRule0-3
[33] DigitalInput_18
[34] DigitalInput_19
[35] DigitalInput_27
[36] DigitalInput_29
[38] DigitalInput_33
*[39] StartCommand
[40] DriveStopped
13-02 Stop Event
See par. 13-01 * [40] DriveStopped
13-03 Reset Logic Controller
*[0] Do not reset
[1] Reset Logic Controller
AF-60 LP Micro Drive
DEH-41264A
13
1