13-1X Comparators
13-10 Comparator Operand
*[0] Disabled
[1] Reference
[2] Feedback
[3] MotorSpeed
[4] MotorCurrent
[6] MotorPower
[7] MotorVoltage
[8] DCLinkVoltage
[12] AnalogInput53
[13] AnalogInput60
[18] PulseInput33
[20] AlarmNumber
[30] CounterA
[31] CounterB
13-11 Comparator Operator
[0] Less Than
*[1] Approximately equals
[2] Greater Than
13-12 Comparator Value
-9999 - 9999 * 0.0
13-2X Timers
13-20 LC Controller Timer
0.0 - 3600 s * 0.0 s
13-4X Logic Rules
13-40 Logic Rule Boolean 1
See par. 13-01 * [0] False
[30] - [32] LC Time-out 0-2
13-41 Logic Rule Operator 1
*[0] Disabled
[1] And
[2] Or
[3] And not
[4] Or not
[5] Not and
[6] Not or
[7] Not and not
[8] Not or not
13-42 Logic Rule Boolean 2
See par. 13-40 * [0] False
13-43 Logic Rule Operator 2
See par. 13-41 * [0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-40 * [0] False
13-5X States
13-51 LC Controller Event
See par. 13-40 * [0] False
13-52 LC Controller Action
*[0] Disabled
[1] NoAction
[2] SelectSetup1
[3] SelectSetup2
[10-17] SelectPresetRef0-7
[18] Select Accel/Decel 1.
[19] Select Accel/Decel 2.
[22] Run
[23] RunReverse
[24] Stop
[25] Qstop
[26] DCstop
[27] Coast
[28] FreezeOutput
[29] StartTimer0
[30] StartTimer1
[31] StartTimer2
[32] Set Digital Output A Low
[33] Set Digital Output B Low
[38] Set Digital Output A High
[39] Set Digital Output B High
[60] ResetCounterA
[61] ResetCounterB
14-XX Special Functions
14-0X Carrier Frequency
14-01 Motor Noise
(Carrier Frequency)
[0] 2 kHz
*[1] 4 kHz
[2] 8 kHz
[4] 16 kHz
14-03 Overmodulation
[0] Off
*[1] On
14-1X Mains monitoring
14-12 Function at mains imbalance
*[0] Trip
[1] Warning
[2] Disabled
14-2X Trip Reset
14-20 Reset Mode
*[0] Manual reset
[1-9] AutoReset 1-9
[10] AutoReset 10
[11] AutoReset 15
[12] AutoReset 20
[13] Infinite auto reset
14-21 Automatic Restart Time
0 - 600 s * 10 s
14-22 Restore Factory Settings
*[0] Normal Operation
[2] Restore Factory Settings
14-26 Action At Drive Fault
*[0] Trip
[1] Warning
14-4X Energy Savings
14-41 Energy Savings Minimum Magnetisation
40 - 75 % * 66 %
15-XX Drive Information
15-0X Operating Data
15-00 Operating Days
15-01 Running Hours
15-02 kWh Counter
15-03 Power Ups
15-04 Over Temps
15-05 Over Volts
15-06 Reset kWh Counter
*[0] Do not reset
[1] Reset counter
15-07 Reset Running Hours Counter
*[0] Do not reset
[1] Reset counter
15-3X Fault Log
15-30 Fault Log: Error Code
15-4X Drive Identification
15-40 GE Drive Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-46 Frequency Converter Order. No
15-48 Keypad Id No
15-51 Frequency Converter Serial No
16-XX Data Readouts
16-0X General Status
16-00 Control Word
0 - 0XFFFF
16-01 Reference [Unit]
-4999 - 4999 * 0.000
16-02 Reference %
-200.0 - 200.0 % * 0.0%
16-03 Status Word
0 - 0XFFFF
16-05 Main Actual Value [%]
-200.0 - 200.0 % * 0.0%
16-09 Custom Readout
Dep. on par. 0-31, 0-32 and 4-14
16-1X Motor Status
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage [V]
16-13 Frequency [Hz]
16-14 Motor Current [A]
16-15 Frequency [%]
16-18 Motor Thermal [%]
16-3X Drive Status
16-30 DC Link Voltage
16-34 Heatsink Temp.
16-35 Inverter Thermal
16-36 Drive Nominal current
16-37 Drive Maximum Current
16-38 Logic Controller State
16-5X Ref. / Feedb.
16-50 External Reference
16-51 Pulse Reference
16-52 Feedback [Unit]
16-6X Inputs / Outputs
16-60 Digital Input 18,19,27,33
0 - 1111
16-61 Digital Input 29
0 - 1
16-62 Analog Input 53 (volt)
16-63 Analog Input 53 (current)
16-64 Analog Input 60
16-65 Analog Output 42 [mA]
16-68 Pulse Input [Hz]
16-71 Relay Output [bin]
16-72 Counter A
16-73 Counter B
16-8X Fieldbus / GE Drive Port
16-86 GE Drive Port REF 1
0x8000 - 0x7FFFF
16-9X Diagnosis Readouts
16-90 Alarm Word
0 - 0XFFFFFFFF
16-92 Warning Word
0 - 0XFFFFFFFF
16-94 Ext. Status Word
0 - 0XFFFFFFFF18-XX Extended Motor Data
18-8X Motor Resistors
18-80 Stator Resistance (High resolution)
0.000 - 99.990 ohm * 0.000 ohm
18-81 Stator Leakage Reactance(High resolution)
0.000 - 99.990 ohm * 0.000 ohm