EasyManua.ls Logo

GE 7FA.05 - AC Motors; Couplings; Unit Piping Systems; Fuel, Oil, Water and Air

GE 7FA.05
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK 116862 Inspection and Maintenance Instructions for 7FA.05 Gas Only and Dual Fuel Gas Turbines
Check operation and timing of the staged resistance starting system. A high speed chart recorder and
DC current probe (or equivalent equipment) are required to perform these checks. Motor current
should not exceed 5 times nameplate current or 66% of circuit breaker trip settings. The motor should
reach operating speed as fast as possible without violating these requirements. The staged contactor
drop out times should not vary from drawing by more than 0.5 seconds.
B. AC Motors
Examine the collector rings, brushes, brush holders and studs for cleanliness and wear. Collector
rings should maintain their polished surface. Brushes should move freely within their holders, but set
firmly in contact with the collector rings. Be sure the pigtail conductors are securely fastened to the
brush holders. Check the insulation for cleanliness and wear.
Periodic greasing of some motors required. See manual for specific greasing instructions. Check
motor insulation resistance and verify functionality of motor heaters if applicable.
Check the vibration of the motor while it is coupled to the pump. The vibration should not exceed 3
mils (0.08 m). Check the cooling passages and louvers of the motor to make sure they are clean,
undamaged and unobstructed.
VII. COUPLINGS
Inspect couplings between motors and/or between motors and pumps for deterioration, missing or loose
hardware and cleanliness. Refer to the Operation and Maintenance Manual under systems for further
information.
VIII. UNIT PIPING SYSTEMS
A. Fuel, Oil, Water and Air
A walk around visual inspection should be made to check piping systems for leaks, loose hardware,
loose hangers, leaky gaskets, valve packing leaks, vibration of piping, vents functioning and a general
check for security of the systems. Corrective action should be taken to correct any abnormalities
found.
B. Flexible Metal Hoses (FMH)
The exterior of the FMH and the flange faces should be observed for any obvious signs of wear or
damage. For FMH that have an external armor covering, small nicks and dings may be acceptable
provided the armor is not against the internal braids. However, signs of rubbing or holes in the armor
should be investigated further.
For FMH without armor, the exterior of the braid should be carefully observed for any signs of
damage or wear. Signs of damage to the armor or braids should result in the FMH being replaced.
22
© General Electric Company, 2011. GE Proprietary Information. All Rights Reserved.

Table of Contents