4–8 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE CHAPTER 4: SETPOINTS
Figure 4-4: Comparing the setpoints for Regular and Simplified mode
Example 2: More about the Function/Feature view control
The differences in the Input setpoints screens for Regular and Simplified mode are shown
below. Under Simplified mode, the Virtual Inputs and Remote Inputs are hidden for any
configuration change. However, the device will still accept and process virtual and remote
inputs based on what is configured during Regular mode. This way, Simplified
configuration mode does not change the behavior of the device.
Figure 4-5: Comparing the Inputs screens for Regular and Simplified mode
Path: Setpoints > Device > Config Mode
CONFIG MODE
Range: Simplified, Regular
Default: Regular
This setting allows selection of the configuration mode while the device is accessed by
the “Administrator” role. In Regular configuration mode, all values in settings/functions
can be edited. In Simplified configuration mode, selected settings/functions are hidden
or the values are read-only to enhance User eXperience (UX) with minimum setpoint
changes.
5HJXODr
Simplified
..\Current\Phase TOC 1
Item Name Value Unit
Function Disabled
Signal Input CT Bank 1 -J1
Input Phasor
Pickup 1.000 x CT
Curve IEEE Mod Inverse
TDM 1.00
Reset Instantaneous
Direction Disabled
Voltage Restraint Disabled
Volt Lower Limit 0.1 p.u.
Block Off
Relays Do Not Operate
Events Enabled
Targets Self-Reset
PTOC 1
..\Current\Phase TOC 1
Item Name Value Unit
Function Disabled
Signal Input CT Bank 1 -J1
Pickup 1.000 x CT
Curve IEEE Mod Inverse
TDM 1.00
Reset Instantaneous
Direction Disabled
Voltage Restraint Disabled
Relays Do Not Operate
PTOC 1
5HJXODr
Simplified
..\Setpoints\Inputs
Item Name
Contact Inputs
Virtual Inputs
Analog Inputs
Remote Inputs
Inputs V Inputs MA In Rem In
..\Setpoints\Inputs
Item Name
Contact Inputs
Analog Inputs
Inputs MA In