4–56 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE CHAPTER 4: SETPOINTS
AUTORESET DELAY
Range: 0.2 to 600.0 s in steps of 0.1 s
Default: 1.0 s
This setting specifies the time delay for automatic Reset of the pushbutton when in the
“Latched” mode.
LOCK
Range: Off, Any FlexLogic operand
Default: Off
This setting assigns a FlexLogic operand serving to inhibit pushbutton operation from
the front panel pushbuttons. This locking functionality is not applicable to pushbutton
autoreset.
DROPOUT TIME
Range: 0.0 to 600.0 s in steps of 0.1 s
Default: 0.0 s
This setting applies only to “Self-reset” mode and specifies the duration of the
pushbutton “active” status after the pushbutton has been released. The length of time
the operand remains on has no effect on the pulse duration.
The setting is required to set the duration of the pushbutton operating pulse.
EVENTS
Range: Disabled, Enabled
Default: Enabled
Table 4-18: PB1 to PB3 Default Values (Membrane and Rugged Front Panels)
PB1 PB2 PB3
Function Self-Reset Self-Reset Self-Reset
ID Text Start Stop F1
ON Text PB1 ON PB2 ON PB3 ON
OFF Text PB1 OFF PB2 OFF PB3 OFF
LED Trigger PB1 ON PB2 ON PB3 ON
Hold Pressed 0.1s 0.1s 0.1s
Autoreset Disabled Disabled Disabled
Autoreset Delay 1.0s 1.0s 1.0s
Lock Off Off Off
Dropout Time 0.0s 0.0s 0.0s
Events Enabled Enabled Enabled