CHAPTER 1: INTRODUCTION 869 ORDER CODES
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 1–9
Figure 1-3: 869 Order Codes
869 E ** ** ** H * * A * N G * * * * * * * * * N *
Interface 869 | | | | |||||||||||||||||| 869 Motor Protection System
Application E | | | | | | | | | | | | | | | | | | | | | Standard
Phase Currents ³
Slot J Bank 1/2
P1| ||||||||||||||||||| 1A three-phase current inputs (J1)
P5| ||||||||||||||||||| 5A three-phase current inputs (J1)
Phase Currents ³
Slot K Bank 1
NN | | | | | | | | | | | | | | | | | | | No phase current inputs
P1 | | | | | | | | | | | | | | | | | | | 1A three-phase current inputs (K1)
P5 | | | | | | | | | | | | | | | | | | | 5A three-phase current inputs (K1)
Ground Currents G1 |||||||||||||||||| 1A ground input (J1)
G5|||||||||||||||||| 5A ground input (J1)
B1||||||||||||||||||
1A ground (J1) + 50:0.025A
(K1, included with current protection M option only)
B5||||||||||||||||||
5A ground (J1) + 50:0.025A
(K1, included with current protection M option only)
0B|||||||||||||||||| 50:0.025A (J1), only available if NN is selected for Slot K Bank 1
Power Supply L | | | | | | | | | | | | | | | | | 24 to 48 V DC
H | | | | | | | | | | | | | | | | | 110 to 250 V DC/110 to 230 V AC
Slot B - LV IO N |||||||||||||||| None
R|||||||||||||||| 6 X RTDS (Pt100, Ni100, Ni120)
S|||||||||||||||| 6 X RTDS (Pt100, Ni100, Ni120, Cu10)
Slot C- LV IO N | | | | | | | | | | | | | | | None
R | | | | | | | | | | | | | | | 6 X RTDS (Pt100, Ni100, Ni120)
S | | | | | | | | | | | | | | | 6 X RTDS (Pt100, Ni100, Ni120, Cu10)
Slot F - HV IO A
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low/High Voltage, Int/Ext
Supply)
Slot G - HV IO N | | | | | | | | | | | | | None
A | | | | | | | | | | | | | 2 Form A, 3 Form C, 7 Digital Inputs (Low/High Voltage, Int/Ext Supply)
L | | | | | | | | | | | | | 7 DcmA O/P + 4 DcmA I/P + 1 RTD
Slot H - HV IO N |||||||||||| None (High Voltage I/O)
F|||||||||||| 10 Digital Inputs + 4 Arc Flash Inputs
A|||||||||||| 2 Form A, 3 Form C, 7 Digital Inputs (Low/High Voltage, Int/Ext Supply)
Faceplate M | | | | | | | | | | | Basic = Membrane Keypad
G | | | | | | | | | | | Standard = Rugged Keypad
Current Protection S | | | |||||||
Basic: 12/14, 19, 37, 38, 46, 49, 50P, 50N, 50G, 50_2, 50LR(Mechanical
Jam), 51P, 51N, 51G, 66, 86
M|||||||||| Standard: Basic + 67P, 67N, 87S (2nd CT Bank required for 87S)
Voltage Monitoring and Protection S | | | | | | | | | Standard: 27P, 27X, 47, 59P, 59N, 59X, 81O, 81U, VTFF
P | | | | | | | | | Advanced : Standard + 32, 40, 40Q, 55, 59_2, 78
Control B | ||||||| Basic: Breaker/Contactor Control, Virtual Inputs
F|||||||| Standard: Basic + FlexLogic, 50BF, Trip Bus
T||||||||
Advanced HMI: Standard + Tab PBs, Annunciator Panel, Configurable
SLDs with Bay Control
Monitoring B
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Basic: Motor Health Report, Motor Start Report, Motor Learned Data,
Data Logger, Breakers Coil Monitoring, Breaker Arcing, Harmonics,
THD, Demand
C | | | | | | | Standard: Basic + Breaker Health Report, Broken Rotor Bar
A | | | | | | | Advanced: Standard + Harmonic Detection, Stator Inter-turn Fault
E | | | | | | | Extended: Advanced + ESA Functions
Communications S E
|
|
|
|
|
|
|
|
|
|
Standard: Front USB, 1 x Rear RS485: Modbus RTU, DNP3.0, IEC60870-
5-103 + 1 x Ethernet (Modbus TCP, DNP)
1E
|
|
|
|
|
|
|
|
|
|
Advanced: Front USB, 1 x Rear RS485 + 2 x Ethernet Fiber, MODBUS
RTU/TCP, DNP3.0, IEC 60870-5-103/104, 1588, SNTP, OPC-UA
1P||||| Advanced + PRP
2A||||| Advanced + IEC 61850
2E||||| Advanced + PRP + IEC 61850
3A||||| Advanced + Extended IEC 61850
3E||||| Advanced + PRP + Extended IEC 61850
Advanced Communications Connector N | | | | None
S | | | | ST, Multi-mode 1310 nm
C | | | | RJ45, Copper 10/100M

Table of Contents

Other manuals for GE 869