CHAPTER 4: SETPOINTS PROTECTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–141
ALARM PICKUP DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a time delay for the alarm function.
ALARM DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a time delay to reset the alarm command.
ALARM OUTPUT RELAY X
For details see Common Setpoints
.
BLOCK
Range: FlexLogic Operand
Default: Off
The Current Unbalance can be blocked by any asserted FlexLogic operand.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched