EasyManua.ls Logo

GE 869 - Page 276

GE 869
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–144 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
BLOCK
Range: FlexLogic Operand
Default: Off
The mechanical jam can be blocked by any asserted FlexLogic operand.
OUTPUT RELAY X
For details see Common Setpoints
.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Disabled
Default: Latched

Table of Contents

Other manuals for GE 869

Related product manuals