4–158 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01
Default: 0.00 s
The setting defines the reset delay of the element.
BLOCK
Range: FlexLogic Operand
Default: Off
The Short Circuit can be blocked by any asserted FlexLogic operand.
OUTPUT RELAY X
For details see Common Setpoints
.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched