4–232 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
PICKUP
Range: 0.80 to 4.00 V/Hz in steps of 0.01
Default: 1.05 V/Hz
Enter the Volts per Hertz value (in V/Hz) above which the Volts per Hertz 1 element will
pickup.
CURVE
Range: Definite Time, Inverse A, Inverse B, Inverse C, FlexCurve A, FlexCurve B,
FlexCurve C, FlexCurve D
Default: Definite Time
Definite Time:
For the definite time curve, T(s) = TD multiplier. For example, setting the TD multiplier to
20 results in a time delay of 20 seconds to operate when above the Volts/Hz pickup
setting. Instantaneous operation can be obtained the same way by setting the TD
multiplier to “0”.
Inverse Curve A:
The curve for the Volts/Hertz Inverse Curve A shape is derived from the formula:
where: T = Operating Time
TDM= Time Delay Multiplier (delay in seconds)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)
The volts/hertz inverse A curves are shown below.
3LFNXS
)
9
ZKHQ
3LFNXS
)
9
7'0
7 !
»
¼
º
«
¬
ª
¸
¹
·
¨
©
§
`
1
2