4–254 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-99: Underfrequency Protection logic diagram
LED: PICKUP
Current Inputs
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
UNDERFREQ 1
FUNCTION :
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
None
Positive -
sequence
SETPOINTS
UNDERFREQ 1
MINIMUM CURRENT :
I = MINIMUM
SETPOINTS
UNDERFREQ 1
MINIMUM VOLTAGE :
AND
SETPOINTS
UNDERFREQ 1 PICKUP :
0 < f = PICKUP
FREQUENCY f
RUN
SETPOINTS
UNDERFREQ 1
PICKUP DELAY :
t
PKP
t
DPO
UNDERFREQ 1
DROPOUT DELAY :
Underfreq 1 OP
FlexLogic Operands
Underfreq 1 PKP
AN D AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
WYE DELTA
VA
VAB
VB VBC
VC VCA
Vx
RUN
V = MINIMUM
RUN
SETPOINTS
OUTPUT RELAY 3 (X)
Do Not Operate , Operate
S
LATCH
Set-
Dominant
R
SETPOINTS
UNDERFREQ 1
SIGNAL INPUT
:
Positive-
sequence
Composite
Voltage Inputs
892737A3.cdr

Table of Contents