CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–269
Figure 4-109: Close Circuit Monitoring Diagram
SETPOINT
CCM
FUNCTION:
Disabled
Alarm
OR
OR
AND
Latched Alarm
LED: ALARM /
LATCHED ALARM
RESET
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operand
Close Coil Mon 1 OP :
SETPOINTS
Do Not Operate , Operate
OUTPUT RELAY X
SETPOINT
CCM
BLOCK :
Off = 0
AND
SETPOINT
CCM
PICK-UP DELAY:
SETPOINT
CCM
BYPASS BKR STATE :
Disabled = 0
FlexLogic Operand
Close Coil Mon 1 PKP :
OR
t PKP
t RST
CCM
DROP-OUT DELAY:
SETPOINT
CCM
BKR STATUS OPENED:
Off = 0
AND
OUTPUT RLY #2
MONITORING VOLTAGE <
THRESHOLD
OUTPUT RLY #2
“CLOSE” OPERATE
89
$1.cdr