EasyManua.ls Logo

GE 869

GE 869
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–315
Figure 4-132: Digital Counter logic diagram
SETPOINT
DGTL CNTR 1
FUNCTION:
Disabled
Enabled
FlexLogic Operand
COUNTER 1 EQL
CALCULATE
ACCUMULATED VALUE
SETPOINTS
Do Not Operate, Operate
SETPOINTS
DGTL CNTR 1 PRE-SET:
SETPOINT
DGTL CNTR 1
BLOCK:
OFF=0
AND
SETPOINT
DGTL CNTR 1
UP:
OFF=0
SETPOINT
DGTL CNTR 1
DOWN:
OFF=0
SETPOINT
DGTL CNTR 1
SET TO PRE-SET:
OFF=0
SETPOINT
DGTL CNTR 1
RESET:
OFF=0
SETPOINT
DGTL CNTR 1
FREEZE/RESET:
OFF=0
SETPOINT
DGTL CNTR 1
FREEZE/COUNT:
OFF=0
OROR
AND AND
SET TO PRE-SET VALUE
SET TO 0
RUN
STORE DATE AND TIME
SETPOINT
DGTL CNTR 1
COMPARE:
COUNT = COMPARE
COUNT < COMPARE
DGTL CNTR 1 NAME:
DGTL CNTR 1 UNITS:
COUNT > COMPARE
FlexLogic Operand
COUNTER 1 LOW
SETPOINTS
Do Not Operate, Operate
FlexLogic Operand
COUNTER 1 HI
SETPOINTS
Do Not Operate, Operate
CNTR 1 HI
OUTPUT RELAY 3 (X)
CNTR 1 EQL
OUTPUT RELAY 3 (X)
CNTR 1 LOW
OUTPUT RELAY 3 (X)
RECORDS
COUNTER 1 FROZEN
COUNTER 1 FROZEN
DATE AND TIME
COUNTER 1
ACCUMULATION
FlexLogic Operand
COUNTER 1 LIMIT
COUNTER REACHED
LIMITS
892751A1.cdr

Table of Contents

Other manuals for GE 869

Related product manuals