4–318 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING CHAPTER 4: SETPOINTS
Figure 4-133: Harmonic Detection logic diagram
894000A2.cdr
LED: PICKUP
SETPOINT
BLOCK :
Off=0
AND
SETPOINT
FUNCTION :
Disabled
Alarm
Latched Alarm
Configurable
OR
SETPOINT
PICKUP :
W1_HDF PICKUP
RUN
SETPOINT
PICKUP DELAY :
t
PKP
0
W1 Harm Derat OP
FlexLogic Operands
W1 Harm Derat PKP
AND AN D
Command
RESET
OR
LED: ALARM
SETPOINT
MINIMUM OPER
CURRENT :
IA MINIMUM
RUN
S
LATCH
Set-
Dominant
R
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
Phase A Harmonics
Phase B Harmonics
Phase C Harmonics
IB MINIMUM
IC MINIMUM
SETPOINT
OUTPUT RELAY X
Do Not Operate , Operate
W1 Current Harmonics
W1 Current Input
Calculate Harmonic
Derating Factor
(W1_HDF )
AND
Phase A Harmonics
Phase B Harmonics
Phase C Harmonics
W2 Current Harmonics
Calculate Harmonic
Derating Factor
(W2_HDF)
Phase A Harmonics
Phase B Harmonics
Phase C Harmonics
W3 Current Harmonics
Calculate Harmonic
Derating Factor
(W3_HDF)
Load Limit Reduced
LED: LOAD-LIMIT
REDUCED
W2_HDF < 0.96
W1_HDF < 0.96
W3_HDF < 0.96
OR