4–360 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL CHAPTER 4: SETPOINTS
REMOTE BLOCK OPEN
Range: Off, Any FlexLogic operand
Default: Off
The assertion of the operand assigned to this setpoint prevents the contactor from
opening (stopping the motor).
REMOTE BLOCK CLOSE
Range: Off, Any FlexLogic operand
Default: Off
The assertion of the operand assigned to this setpoint prevents the breaker from closing
(starting the motor).
BYPASS REM BLK OPEN
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies selection of an input which when asserted bypasses the asserted
remote block open (stop motor) signal. The Open (Stop motor) command is permitted for
the contactor.
BYPASS REM BLK CLOSE
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies selection of an input which when asserted bypasses the asserted
remote block open (stop motor) signal. The Open (Stop motor) command is permitted for
the contactor.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Figure 4-160: Contactor Control logic diagram