4–380 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC CHAPTER 4: SETPOINTS
Breaker Health BKR 1 Hlth PKP
BKR 1 Hlth Trip PKP
BKR 1 Hlth Cls PKP
BKR 1 Hlth Chg PKP
BKR 1 Arc PKP A
BKR 1 Arc PKP B
BKR 1 Arc PKP C
BKR 1 Engy PKP A
BKR 1 Engy PKP B
BKR 1 Engy PKP C
BKR 1 Hlth OP Fail
BKR 1 Arc Fail
BKR 1 Charge Fail
Breaker health has picked up
Trip time of breaker health has picked up
Close time of breaker health has picked up
Spring charge time of breaker health has picked up
Arc time of phase A of breaker health has picked up
Arc time of phase B of breaker health has picked up
Arc time of phase C of breaker health has picked up
Arc energy of phase A of breaker health has picked up
Arc energy of phase B of breaker health has picked up
Arc energy of phase C of breaker health has picked up
Breaker trip or close operation has failed
Breaker arc time has failed
Spring charge time has failed
Broken Rotor Bar Brokn Rtr Bar PKP
Brokn Rtr Bar OP
Broken Rotor Bar has picked up
Broken Rotor Bar has operated
Close Circuit Monitoring Cls Coil Mon 1 PKP
Cls Coil Mon 1 OP
Close Coil 1 Monitoring element has picked up.
Close Coil 1 Monitoring element has operated for an amount of time
greater than the Close Circuit Monitor Pick-up Delay Time.
Contact Control Cnct1 Rem Open
Cnct1 Rem Close
Cnct1 Rem Blk Open
Cnct1 Rem Blk Close
Cnct1 Rem Blk Opn By
Cnct1 Rem Blk Cls By
Remote Open command is initiated to Contactor 1
Remote Close command is initiated to Contactor 1
The Open command to Contactor 1 is blocked
The Close command to Contactor 1 is blocked
The block open signal to Contactor 1 is bypassed
The block close signal to Contactor 1 is bypassed
Critical Failure Relay Critical Fail OP The critical failure relay operated
Contact Inputs CI # On
CI # Off
# – any contact input number
Contactor State Detection Contactor Opened
Contactor Closed
Contactor Unkwn Stat
Contactor Connected
Contactor Disconnect
Contactor Configured
Contactor state is detected open
Contactor state is detected closed
Closed or Open Contactor state cannot be detected
Contactor has been connected to the power system
Contactor has been detached from the power system
Contactor status contacts are configured
Current Unbalance Cur Unbal Alarm OP
Cur Unbal OP
Single Phasing OP
Current Unbalance alarm stage operates.
Current Unbalance trip stage operates.
Single Phasing operates.
Demand Current Dmd PKP
Current Dmd PKP A
Current Dmd PKP B
Current Dmd PKP C
RealPwr Dmd PKP
ReactvPwr Dmd PKP
ApprntPwr Dmd PKP
At least one phase from current demand element has picked up
Phase A from current demand element has picked up
Phase B from current demand element has picked up
Phase C from current demand element has picked up
Real power demand has picked up
Reactive power demand has picked up
Apparent power demand has picked up
Digital Counters Counter 1 HI
Counter 1 EQL
Counter 1 LO
Counter 1 at Limit
Counter 2 to Counter 16
Digital counter 1 output is ‘more than’ comparison value
Digital counter 1 output is ‘equal to’ comparison value
Digital counter 1 output is ‘less than’ comparison value
Digital counter 1 reached limit
Same set of operands as for Counter 1
Directional Power DirPwr 1 Stg1 PKP
DirPwr 1 Stg2 PKP
DirPwr 1 PKP
DirPwr 1 Stg1 OP
DirPwr 1 Stg2 OP
DirPwr 1 OP
DirPwr 2
Stage 1 of the directional power element 1 has picked up
Stage 2 of the directional power element 1 has picked up
The directional power element has picked up
Stage 1 of the directional power element 1 has operated
Stage 2 of the directional power element 1 has operated
The directional power element has operated
The same set of operands per DirPwr 1
ELEMENT OPERANDS EVENT DESCRIPTION