4–384 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC CHAPTER 4: SETPOINTS
Relay Service In-Service The relay is In-Service
Remote Input Rem Ip # ON
Rem Ip # OFF
# – any remote input number
Remote Modbus Device FlexLogic Operand [X] On
FlexLogic Operand [X] Off
[X] - the element number. Note the operand name will change depending
on what is programmed.
Resetting Reset OP
Reset OP (PB)
Reset OP (Operand)
Reset OP (Comms)
Reset command
Reset command initiated from a front panel pushbutton
Reset command initiated from a FlexLogic operand
Reset command initiated via communications
RTD Temperature RTD 1 Trip PKP
RTD 1 Trip OP
RTD 1 Alarm PKP
RTD 1 Alarm OP
RTD 1 Open
RTD 1 Shorted
RTD 1 Trip has picked up. It is displayed as “RTD 1 PKP” if the Trip Function
is set to “Configurable”.
RTD 1 Trip has operated. It is displayed as “RTD 1 OP” if the Trip Function is
set to “Configurable”.
RTD 1 Alarm has picked up
RTD 1 Alarm has operated
RTD 1 sensor is detected open
RTD 1 sensor is detected shorted
RTD 2 to RTD 12 Similar to RTD 1
Hot RTD Any RTD Alarm PKP operand has picked up.
RTD Trouble RTD Trouble PKP
RTD Trouble OP
RTD Trouble has picked up
RTD Trouble has operated
Security ROLE ADMIN ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
Administrator role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Self-Test Error Any Minor Error
Any Major Error
see the Relay Minor Self-Test errors table
see the Relay Major Self-Test errors table
Setpoint Access Setpoint Access OP An access to change setpoints has been granted
Setpoints Group Control Group 1 Active
Group 2 Active
…
Group 6 Active
Setpoint group 1 is active
Setpoint group 2 is active
…
Setpoint group 6 is active
Short Circuit Short Circuit PKP
Short Circuit OP
The short circuit element has picked up
The short circuit element has operated
Speed2 Motor Protection Speed2 TR 2-1 OP
Motor Speed 2
Spd2 Accel Time OP
Spd2 U/C ALM PKP
Spd2 U/C ALM OP
Spd 2 U/C PKP
Spd 2 U/C OP
Asserted when the motor switches from speed 2 to speed 1
The motor is running at speed 2
The speed 2 acceleration time element has operated
The speed 2 undercurrent alarm has picked up
The speed 2 undercurrent alarm has operated
The speed 2 undercurrent has picked up
The speed 2 undercurrent has operated
Speed Protection Speed Trip PKP
Speed Trip OP
Speed Alarm PKP
Speed Alarm OP
Speed Trip has picked up
Speed Trip has operated
Speed Alarm has picked up
Speed Alarm has operated
Start Supervision Thermal Inhibit PKP
Thermal Inhibit OP
Max Start Rate PKP
Max Start Rate OP
Time Btwn Star PKP
Time Btwn Start OP
Restart Delay PKP
Restart Delay OP
Start Inhibit
Thermal Inhibit has picked up.
Thermal Inhibit has operated.
Maximum Starting Rate has picked up.
Maximum Starting Rate has operated.
Time Between Start has picked up.
Time Between Start has operated.
Restart Delay has picked up.
Restart Delay has operated.
Any Start Inhibit has operated: Thermal Inhibit OR Maximum Starting Rate
OR Time Between Start OR Restart Delay OR Phase Rev Inhibit
Stator Inter Turn Fault Stat Trn Flt 1 PKP
Stat Trn Flt 1 OP
Stat Trn Flt 2 PKP
Stat Trn Flt 2 OP
Stator Inter Turn Fault stage 1 has picked up
Stator Inter Turn Fault stage 1 has operated
Stator Inter Turn Fault stage 2 has picked up
Stator Inter Turn Fault stage 2 has operated
Tab Pushbuttons TAB PB [X] ON
TAB PB [X] OFF
TAB PB [X] PRESS
Tab Pushbutton [X] is ON
Tab Pushbutton [X] is OFF
Tab Pushbutton [X] is Pressed Down
Targets Active Target At least one target is detected active
ELEMENT OPERANDS EVENT DESCRIPTION