EasyManua.ls Logo

GE 869 - Page 529

GE 869
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS FLEXLOGIC
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–397
PF
BASE
= 1.00
FlexElement can be programmed to switch-in cap bank, if for example the measured 3Ph
Power Factor has negative value(lag), and drops below the pickup of -0.7 pu. Programming
the Hysteresis setpoint to the desired percentage can define the PF value at which the cap
bank can be switched off. For example, if the cap bank is required to be switched off at PF
value of -0.9, than the percent hysteresis is computed as:
% hysteresis = ((abs(-0.9)-abs(-0.7))/ PFBASE)*100 = 20%
FAST PATH:
The minimum pickup should not be less than 0.01 pu, as the measurement resolution for
the Power Factor is 0.01.
Input 1(+): Pwr1 PF
Input 2(-): Off
Operating Mode: Signed
Input Comparison Mode: Level
•Direction: Under
Pickup: -0.700 pu
Hysteresis: 20.0 %
Detecting high THD (Total Harmonic Distortion)
THD
BASE
= 100%
A FlexElement can be programmed to detect excessive amount of harmonics in the
system, and Alarm, Trip, or switch-in/out an equipment to suppress the high amount of
harmonics. The Total Harmonic Distortion is an estimation of how the AC signals are
distorted and as shown above, it can be used as an input for the FlexElement.
For example if an operation from a FlexElement is desired when the THD for the phase A
voltage exceeds 20%, then having a base of 100%, the pickup setting should be set to
0.200 pu.
Input 1(+): J2 Phase A THD
Input 2(-): Off
Operating Mode: Absolute
Input Comparison Mode: Level
Direction: Over
Pickup: 0.200 pu
FAST PATH:
The harmonics and THD values are measured as percentage of the fundamental signal,
and have resolution of 0.01%. However for the minimum pickup setting of 0.001 pu, this
would mean percentage step of 0.1%.
Simple V/Hz ratio detection for protected equipment
V/Hz
BASE
= 1.00High V/Hz ratios in the power system are harmful for the insulation of the
protected equipment – transformer, generator, or elsewhere in the power system. If not
detected, it can lead to excessive heat and degradation of the insulation which will
damage the equipment. A FlexElement can be used for simple detection of V/Hz values,
and to issue an Alarm, or Trip, if detected above Pickup setting. Since the base unit for V/Hz
= 1.00, programming of the pickup setpoint is straight forward for the desired FlexElement
operation. For the example given here, a value of 1.200 pu has been selected.
Input 1(+): Volts Per Hertz 1Input 2(-): OffOperating Mode: AbsoluteInput Comparison
Mode: LevelDirection: OverPickup: 1.200 puHysteresis: 8.3 %
Now, if the FlexElement is needed to drop down when the V/Hz ratio becomes equal to 1.1,
the hysteresis can be calculated as:1.2pu-1.1pu = 0.1 puHysteresis = (0.1*100)/1.2 = 8.3%
RTD inputs for Top-Bottom oil temperature on Transformer

Table of Contents

Other manuals for GE 869

Related product manuals