CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3–7
The Breaker/Contactor and motor status color is based on the following logic.
Figure 3-8: Breaker/Contactor and Motor status color
Regardless of the switching device selection (System > Motor > Setup > Switching Device),
the breaker/contactor colors will follow the color scheme setting (
Setpoints > Device >
Front Panel > Display Properties > Color Scheme). By default, the “Green (Open)” setting is
selected.
The parameters displayed in the Front panel screen example are as follows:
Parameter Input for the value
Ia Metering\CT Bank 1 -J1\J1 Ia
Ib Metering\CT Bank 1 -J1\J1 Ib
Ic Metering\CT Bank 1 -J1\J1 Ic
Ig Metering\CT Bank 1 -J1\J1 Ig
Ep Metering\Energy 1\Pwr1 Pos WattHours
Eq Metering\Energy 1\Pwr1 Pos VarHours
P Metering\Power 1\Pwr1 Real
Q Metering\Power 1\Pwr1 Reactive
PF Metering\Power 1\Pwr1 PF
SLD Breaker/Contactor symbol Color Motor Status
Color Scheme Open Color Close Color
Not
Configured
Unknown Disconnected Stopped Starting Running Overload Tripped
Red (Open)
Red Green Green Red Orange
Green (Open)
Green Red Red Green Orange