CHAPTER 3: INTERFACES SOFTWARE INTERFACE
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3–33
Figure 3-17: Quick Setup window
Settings names and units can be viewed at this screen. To view the range of the
settings, hover the cursor over the setpoint value field.
The user can configure and save the settings as required.
The Save, Restore and Default buttons function the same as in the individual setting
setup screens.
Attempting to enter and save a setting value which exceeds the range gives a
warning dialog box. (note the value is not replaced with the maximum value of the
setting). The user must correct the setting value and save to proceed.
Example:The Phase CT Primary value has a setting range of 1 to 12000, but the user
enters 12001 and tries to save it. Quick Setup displays a warning dialog. Pressing OK
leaves the setting value at 12001, but not 12000 (max. value) as is the case with other
views.