CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–251
Power Elements
Figure 4-98: Power Elements Display Hierarchy
Directional Power (32) The 889 relay provides two identical Directional Power elements per protection group; a
total of 12 elements.
The Directional Power element responds to three-phase directional power and is designed
for reverse power (32REV) and low forward power (32FWD) applications for synchronous
machines or interconnections involving co-generation. The relay measures the three-
phase power from either a full set of wye-connected VTs or a full-set of delta-connected
VTs. In the latter case, the two-wattmeter method is used.
The element has an adjustable characteristic angle and minimum operating power as
shown in the Directional Power characteristic diagram. The element responds to the
following condition:
Where:
P and Q are active and reactive powers as measured per the metering convention
Ɵ is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR
POWER 1 CALIBRATION) angles
SMIN is the minimum operating power.
The element has two independent (as to the Pickup and Delay settings) stages for Alarm
and Trip, and they can be set separately to provide mixed power protection.
Level 1 Level 2 Level 3 Level 4 Level 5
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
Directional Power
Data Capture
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Data Capture
Power
Frequency
Impedance
Voltage
Generator
Current
Reactive Power
FlexL
Testing

Table of Contents

Related product manuals