4–38 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE CHAPTER 4: SETPOINTS
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists > Analog Input / MME 
Points
Analog IP Point 0 Entry
Point 0 Scale Factor
Point 0 Deadband
DNP ANALOG INPUT POINT 0(31) SCALE FACTOR
Range: / 0.001, / 0.01, / 0.1, / 1, / 10, / 100, / 1000, / 10000, / 100000
Default: /1
These are numbers used to scale analog input point values. Each setting represents the 
scale factor for the analog input point. For example, if the DNP PHASE A VOLTAGE SCALE 
FACTOR setting is set to “/ 1000”, and the Phase A voltage is 72000 V, the Phase A voltage 
is sent on to the 889 as 72. The settings are useful when analog input values must be 
adjusted to fit within certain ranges in DNP masters. 
FAST PATH: 
Note that a scale factor of ”/ 0.1” is equivalent to a multiplier of 10.
DNP ANALOG INPUT POINT 0(31) DEADBAND
Range: 1 to 100000000 in steps of 1
Default: 30000
The setting is the threshold value to define the condition to trigger unsolicited responses 
containing analog input data. Each setting represents the default deadband value for 
the associated analog input. For example, to trigger unsolicited responses from the 
889 when phase A current changes by 15 A, the DNP CURRENT DEADBAND for Phase A 
current should be set to “15”. Note that these settings are the deadband default values. 
DNP object 34 points can be used to change deadband values from the default for each 
individual DNP analog input point. Whenever power is removed and re-applied to the 
889 the new deadbands are in effect.
The binary output points for the DNP protocol, or the CSC/CDC points for IEC 60870-5-104 
protocol, can be configured to a maximum of 16 points. The data source for each point is 
user-programmable and can be configured by assigning FlexLogic operands. The menu 
path for the binary output points (DNP) or CSC/CDC points (IEC 60870-5-104) is shown 
below.
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists > Binary Output / 
CSC/CDC Points
Binary Output Point 0 ON
Binary Output Point 0 OFF
...
Binary Output Point 15 ON
Binary Output Point 15 OFF
FAST PATH: 
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” 
value. Since DNP / IEC 60870-5-104 point lists must be in one continuous block, any points 
assigned after the first “Off” point are ignored.
BINARY INPUT POINTS
The DNP binary input data points are configured through the DNP / IEC104 POINT LISTS 
BINARY INPUT / MSP POINTS menu. When a freeze function is performed on a binary 
counter point, the frozen value is available in the corresponding frozen counter point.
BINARY INPUT POINTS
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status), 
Configurable