EasyManua.ls Logo

GE 889 - Page 254

GE 889
580 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–124 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Logging this data into the CT sat tool, produces the following CT saturation waveform:
The waveform shows that during this external bolted fault with maximum fault current of
25 kA, the CT (3000:5) will saturate severely, and produce only a ¼ of a cycle saturation
free time. Break 2 must be set to a through fault current so that the CT (3000:5) produces at
least ½ cycle saturation free time. The solution is to change the fault current to 15000 kA.
The waveform now shows a bigger part of the first cycle before saturation.
The fault current of 15000 Amps would then be translated as 15000/3000 = 5 times
winding 2 CT. Bringing this to the same scale with respect to winding 1 CT reference , i.e.
multiplying by a magnitude of 0.4521, the Break 2 setting would be:
Break 2 = 5 *0.4521 = 2.21 xCT (w1)

Table of Contents

Related product manuals