4–136 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-47: Inadvertent Energization Logic Diagram
894133.cdr
SETPOINT
BLOCK :
Off=0
AND
SETPOINT
FUNCTION :
Trip
Alarm
Latched Alarm
Configurable
OR
5s
250 ms
Inadv Energ OP
FlexLogic Operands
AND AND
Command
RESET
OR
LED: ALARM
SETPOINT
O/ C PICKUP :
IA > PICKUP
RUN
S
LATCH
Set-
Dominant
R
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
IB > PICKUP
IC > PICKUP
SETPOINT
OUTPUT RELAY X :
Do Not Operate , Operate
Disabled
AN D
J1 Current Inputs
SETPOINT
U/V PICKUP :
VA (VAB ) < PICKUP
RUN
VB (VBC) < PICKUP
VC (VCA) < PICKUP
J2 Voltage Inputs
OR
AN D
SETPOINT
ARMING MODE :
U/V and Offline
U/V or Offline
Offline
FlexLogic Operand
AN D
OR
AND
OR
AND
LED: TRIP
Trip
Inadv Energ Armed
WYE DELTA
VA VAB
VB VBC
VC VCA