EasyManua.ls Logo

GE 889 - Page 283

GE 889
580 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–153
Figure 4-54: Offline Overcurrent Logic Diagram
SETPOINTS
Phase A current (Ia)
RUN
SETPOINTS
FUNCTION:
Disabled = 0
Trip
PICKUP:
AND
Phase B current (Ib)
Phase C current (Ic)
RUN
RUN
Operate Output Relay 1 (TRIP)
LED: PICKUP
Alarm
OR
OR
AND
Latched Alarm
AND
BLOCK
Off = 0
Ib > PICKUP
Ia > PICKUP
Ic > PICKUP
SETPOINTS
t
PKP
t
PKP
t
PKP
OR
OR
LED: ALARM
RESET
Command
AND
S
R
LATCH
Configurable
Offline OC OP
Offline OC OP A
Offline OC OP B
Offline OC OP C
FlexLogic Operands
Offline OC PKP
Offline OC PKP A
Offline OC PKP B
Offline OC PKP C
FlexLogic Operands
SETPOINTS
OUTPUT RELAYS 2 to X
Do Not Operate, Operate
0
0
0
PICKUP DELAY:
LED: TRIP
Set
Dominant
SETPOINTS
Signal Input
SETPOINTS
AND AND
OFFLINE
FlexLogic Operand
CT BANK 1-J1
CT BANK 1-K1
TRIPPED
FlexLogic Operand
OR
894131.cdr

Table of Contents

Related product manuals