CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–171
Figure 4-60: Phase Directional Overcurrent Protection logic diagram
894156A2.cdr
SETPOINT
FUNCTION:
Disabled = 0
Enabled = 1
SETPOINT
BLOCK:
Off = 0
Voltage Polarization
Vpol
FWD
REV
RUN
SETPOINT
ECA
I > 0.05 x CT
AND
OR
ACTUAL VALUES
Ia
Seq = ABC Seq = ACB
Vbc Vcb
SETPOINT
REV WHEN V MEM EXP
No
Yes
SETPOINT
POLARIZING V TRESHOLD
Vact if V>= V minimum
Vmem if V< Vminimum
V>= V minimum
MEMORY TIMER
1 cycle
1 sec
AND
AND
PHASE B LOGIC SIMILAR TO PHASE A
PHASE C LOGIC SIMILAR TO PHASE A
Ph Dir OC REV A
FLEXLOGIC OPERANDS
Ph Dir OC REV B
FLEXLOGIC OPERANDS
Ph Dir OC REV C
FLEXLOGIC OPERANDS
To phase TOC & IOC
elements
To phase TOC & IOC
elements
To phase TOC & IOC
elements
OR
Ph Dir OC REV
FLEXLOGIC OPERANDS
SETPOINTS
SIGNAL INPUT:
CT Bank 1 - J1

Table of Contents