CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–191
Figure 4-67: Ground Directional Overcurrent Protection logic diagram
894157A1.cdr
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETTING
SETTING
SETTING
SETTING
SETTINGS
SETTING
SETTING
GROUND
FUNCTION :
DIR OC
GROUND
VOLT :
DIR OC POL
GROUND
POLARIZING :
DIR OC
BLOCK :
GROUND
LIMIT ANGLE :
DIR OC FWD
GROUND
ECA:
DIR OC FWD
GROUND
LIMIT ANGLE :
DIR OC REV
GROUND DIR OC FWD
PICKUP:
GROUND
PICKUP:
DIR OC REV
Gnd Dir OC FWD
Gnd Dir OC REV
Disabled=0
Measured VX
Voltage
Calculated V _0
}
}
Current
Ground Crt (Ig)
K1-CT Crt (Ipol)
Dual
NOTE:
CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE
Off=0
Enabled=1
AND
AND
AND
AND
AND
AND
AND
OR
OR
OR
OR
Ipol 0.05xCT
Ig PICKUP
Ig PICKUP
Voltage Polarization
Current Polarization
-3V_0
3I_0
FWD
FWD
FWD
REV
REV
REV
RUN
RUN
RUN
RUN
1.25 cy
1.5 cy
TO GROUND TOC AND
IOC ELEMENTS
TO GROUND TOC AND
IOC ELEMENTS
AND
SETPOINTS
SIGNAL INPUT :
CT Bank 1 - J1
USED ONLY IN 845 and 889
894157A1.cdr