4–214 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-78: Negative Sequence Directional Overcurrent Protection logic diagram
AND
AND
AND
AND
NOTE:
V_2 is negative-sequence voltage
I_2 is negative-sequence current
AND
SETTING
Off = 0
Block
SETTINGS
Forward Pickup
Positive-Sequence Restraint
TIMER
1.25 cycles
1.5 cycles
FLEXLOGIC OPERAND
NegSeq DirOC FWD
SETTING
Disabled = 0
Enabled = 1
Function
ACTUAL VALUES
V_2
I_2
RUN
( |I_2| × |I_1| ) PickupK
Voltage Polarization
SETTINGS
Forward ECA
RUN
Forward Limit Angle
Reverse Limit Angle
Forward
Reverse
SETTINGS
Reverse Pickup
RUN
( |I_2| × |I_1| ) PickupK
Pos Seq Restraint
FLEXLOGIC OPERAND
NegSeq DirOC REV
892725A1.cdr
TO NEG SEQ TOC AND
IOC ELEMENTS
TO NEG SEQ TOC AND
IOC ELEMENTS