CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–233
Figure 4-88: Auxiliary Overvoltage Protection logic diagram
894076A3.cdr
SETPOINTS
Auxiliary Voltage (Vx)
SETPOINT
FUNCTION:
Disabled
Trip
PICKUP:
AND
Operate Output Relay 1 (TRIP)
LED: TRIP
Alarm
OR
OR
Auxiliary voltage
AND
Latched Alarm
AND
Vx > PICKUP
RUN
SETPOINTS
BLOCK :
Off = 0
LED: ALARM /
LATCHED ALARM
RESET
Command
AND
S
R
LATCH
Configurable
FlexLogic Operands
Aux OV OP:
Aux OV PKP:
PICK-UP DELAY:
DROP-OUT DELAY:
LED: PICKUP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAYS 3 to 7
SETPOINTS
SIGNAL INPUT:
NAME( Ax VT Bnk1-J2
889
Overvoltage Curves:
t PKP
t RST