CHAPTER 4: SETPOINTS PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–265
Figure 4-105: Overfrequency Protection logic diagram
LED: PICKUP
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
OVERFREQ 1
FUNCTION :
Disabled
Alarm
Latched Alarm
Configurable
OR
Voltage Inputs
None
SETPOINTS
OVERFREQ 1
PICKUP :
f PICKUP
RUN
SETPOINTS
OVERFREQ 1
PICKUP DELAY :
t
PKP
t
DPO
OVERFREQ 1
DROPOUT DELAY :
Overfreq1 OP
FlexLogic Operands
Overfreq1 PKP
AND AND
Command
RESET
OR
LED: ALARM
SETPOINTS
OVERFREQ 1
MINIMUM OPERATING
VOLTAGE :
V MINIMUM
FREQUENCY f
RUN
SETPOINTS
RELAYS
Do Not Operate , Operate
S
LATCH
Set-
Dominant
R
Trip
AN D
LED: TRIP
Operate Output Relay 1 (TRIP)
WYE
DELTA
VA
VAB
VB VBC
VC VCA
Vx
SETPOINTS
OVERFREQ 1
SIGNAL INPUT
:
Positive -
sequence
Composite
894055A2.cdr