CHAPTER 5: STATUS COMMUNICATIONS
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5–11
NOT RUNNING.ERROR CID
Range: NO, YES
Default: NO
RUNNING.DEFAULT CID
Range: NO, YES
Default: NO
RUNNING.SAVING CID TO FLASH
Range: NO, YES
Default: NO
CID HANDLING DONE
Range: YES, NO
Default: YES
NUMBER OF CONNECTED CLIENTS
Default: 0
CLIENT 1(8) IP ADDRESS
Range: 0, 0XFFFFFFFF
Default: 0
ACTIVITY STATUS
The communication state for each enabled communication type is shown by its value. The
main CPU and Comms software sets/resets the active bits for all enabled communication
types. The communication state bits are not latched.
Path: Status > Communications > Activity Status
SERIAL MODBUS
Range: NONE, ACTIVE
Default: NONE
SERIAL DNP
Range: NONE, ACTIVE
Default: NONE
SERIAL IEC103
Range: NONE, ACTIVE
Default: NONE
ETHERNET MODBUS
Range: NONE, ACTIVE
Default: NONE
ETHERNET DNP
Range: NONE, ACTIVE
Default: NONE
ETHERNET IEC104
Range: NONE, ACTIVE
Default: NONE
ETHERNET IEC61850
Range: NONE, ACTIVE
Default: NONE
ETHERNET GOOSE
Range: NONE, ACTIVE
Default: NONE