
Do you have a question about the GE A-Series II Panelboard and is the answer not in the manual?
| Voltage | 120/240 V |
|---|---|
| Main Type | Main Lug |
| Phase | 1 |
| Enclosure Type | NEMA 1 |
| Interrupting Rating | 10 kA |
Remove all power from the panelboard before attempting installation.
Remove interior assembly, dead front, and circuit breaker kit from packaging and verify parts.
Mount branch bases for A phase adjacent to cross bar and secure with screw [7].
Mount branch bases for B and C phases to main busbar, adjacent to other bases, using screws [7].
Refer to Figure 2 for mounting the breaker on the left side of the interior.
Mount the bracket [8] on the interior rail with screws [9] with specified torque.
Secure spools [4] to the underside of the breaker terminal using screws [5] and conical washer [6].
Place breaker over branch bases, align spool, and tighten screws [5] to branch bases.
Insert screws [14] into the circuit breaker and tighten to bracket [8] with specified torque.
Remove four screws [12] of the existing filler plate from the dead front.
Install filler plate [11] over dead front on left side, align holes, and fasten with screws [12].
Install filler plate [11] over dead front on right side, align holes, and fasten with screws [12].
Reattach the dead front to the interior with the 8 screws removed in step 2.
Install SF breaker after SG, following gap specifications and replacing blank filler with SF filler plate.
Install SF breaker after crossbar, ensuring a 0.061-inch gap between breaker and crossbar.
Loading...