Figure 4. Attaching the shield insert to the shield for SF breaker installation in
A-Series
®
II panelboards.
14. If SF breaker has to be installed after SG as shown in Figure 5 then gap between
the breakers (dim A) has to be followed as mentioned in Table 2. Replace the
subsequent blank filler of dead front with SF filler plate given in kit ASPP6SF3S
using steps 10 to 13.
15. If SF breaker has to be installed immediately after crossbar as shown in Figure 6
then gap between the breaker and crossbar has to be 0.061inch.