Parameter Number Parameter Description Default Value 2 Setup Change During Operation Conversion Index Type
3 - 00 Reference Range [0] Min - Max All set-ups TRUE - Uint8
3 - 02 Minimum Reference 0 All set-ups TRUE -3 Int32
3 - 03 Maximum Reference 50 All set-ups TRUE -3 Int32
3 - 10 Preset Reference 0% All set-ups TRUE -2 Int16
3 - 11 Jog Speed [Hz] 5 Hz All set-ups TRUE -1 Uint16
3 - 12 Catch up/slow Down Value 0% All set-ups TRUE -2 Int16
3 - 14 Preset Relative Reference 0% All set-ups TRUE -2 Int16
3 - 15 Reference Resource 1 [1] Analog in 53 All set-ups TRUE - Uint8
3 - 16 Reference Resource 2 [2] Analog in 60 All set-ups TRUE - Uint8
3 - 17 Reference Resource 3 [11] Local bus reference All set-ups TRUE - Uint8
3 - 18 Relative Scaling Reference Resource [0] No function All set-ups TRUE - Uint8
3 - 40 Accel/Decel 1 Pattern [0] Linear All set-ups TRUE - Uint8
3 - 41 Accel Time 1 3 s All set-ups TRUE -2 Uint32
3 - 42 Decel Time 1 3 s All set-ups TRUE -2 Uint32
3 - 50 Accel/Decel 2 Pattern [0] Linear All set-ups TRUE - Uint8
3 - 51 Accel Time 2 3 s All set-ups TRUE -2 Uint32
3 - 52 Decel Time 2 3 s All set-ups TRUE -2 Uint32
3 - 80 Jog Accel/Decel Time 3 s All set-ups TRUE -2 Uint32
3 - 81 Quick Stop Ramp Time 3 s 1 set-up TRUE -2 Uint32
5.2.8. 3-** Reference/Ramps