CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-81
2
" 6112 87PC Trip Security 0 to 1 --- 1 F534 0 (First
Coincidence)
" 6113 87PC Second Coincidence Timer 10 to 200 ms 1 F001 40
" 6114 87PC Enhanced Stability Angle 40 to 180 ° 5 F001 110
" 6115 87PC FDH Supervision 0 to 4294967295 --- 1 F300 0
" 6117 87PC Pickup Delay 0 to 50 ms 1 F001 0
" 6118 87PC Stop Tx 0 to 4294967295 --- 1 F300 0
" 611A 87PC Tx Reset Delay 0 to 1000 ms 1 F001 0
Continuous Monitor (Read/Write Setting)
L90 6130 Continuous Monitor Function 0 to 1 --- 1 F102 0 (Disabled)
" 6131 Continuous Monitor I (current) OP 0 to 4294967295 --- 1 F300 0
" 6133 Continuous Monitor I (current) Supervision 0 to 4294967295 --- 1 F300 0
" 6135 Continuous Monitor V (voltage) OP 0 to 4294967295 --- 1 F300 0
" 6137 Continuous Monitor V (voltage) Supervision 0 to 4294967295 --- 1 F300 0
" 6139 Continuous Monitor Target 0 to 2 --- 1 F109 0 (Self-reset)
" 613A Continuous Monitor Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Hottest Spot (Read/Write Grouped Setting)
G30, T35, T60 6140 Transformer Hottest Spot Function 0 to 1 --- 1 F102 0 (Disabled)
" 6141 Transformer Hottest Spot Pickup 50 to 300 °C 1 F001 140
" 6142 Transformer Hottest Spot Delay 0 to 30000 min 1 F001 1
" 6143 Transformer Hottest Spot Block 0 to 4294967295 --- 1 F300 0
" 6145 Transformer Hottest Spot Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6146 Transformer Hottest Spot Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Aging Factor (Read/Write Grouped Setting)
G30, T35, T60 6150 Transformer Aging Factor Function 0 to 1 --- 1 F102 0 (Disabled)
" 6151 Transformer Aging Factor Pickup 1 to 10 PU 0.1 F001 20
" 6152 Transformer Aging Factor Delay 0 to 30000 min 1 F001 10
" 6153 Transformer Aging Factor Block 0 to 4294967295 --- 1 F300 0
" 6155 Transformer Aging Factor Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6156 Transformer Aging Factor Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Loss of Life (Read/Write Grouped Setting)
G30, T35, T60 6160 Transformer Loss of Life Function 0 to 1 --- 1 F102 0 (Disabled)
" 6161 XFMR LOL Initial Value 0 to 500000 hrs 1 F003 0
" 6163 Transformer Loss of Life Pickup 0 to 500000 hrs 1 F003 180000
" 6165 Transformer Loss Of Life Block 0 to 4294967295 --- 1 F300 0
" 6167 Transformer Loss of Life Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6168 Transformer Loss of Life Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Thermal Inputs (Read/Write Setting)
G30, T35, T60 6170 Transformer Thermal Model Source Input 0 to 5 --- 1 F167 0 (SRC 1)
" 6171 Ambient Temperature Input Sensor 0 to 32 --- 1 F450 0
" 6172 Top Oil Temperature Input Sensor 0 to 32 --- 1 F460 0
" 6173 January Average Ambient Temperature -60 to 60 °C 1 F002 -20
" 6174 February Average Ambient Temperature -60 to 60 °C 1 F002 -30
" 6175 March Average Ambient Temperature -60 to 60 °C 1 F002 -10
" 6176 April Average Ambient Temperature -60 to 60 °C 1 F002 10
" 6177 May Average Ambient Temperature -60 to 60 °C 1 F002 20
" 6178 June Average Ambient Temperature -60 to 60 °C 1 F002 30
Products Address Register name Range Units Step Format Default