2-86 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 6471 Overfrequency 1 Block 0 to 4294967295 --- 1 F300 0
" 6473 Overfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6474 Overfrequency 1 Pickup 20 to 65 Hz 0.01 F001 6050
" 6475 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
" 6476 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
" 6477 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6478 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6479 Reserved (4 items) 0 to 1 --- 1 F001 0
" 647D ...Repeated for Overfrequency 2
" 648A ...Repeated for Overfrequency 3
" 6497 ...Repeated for Overfrequency 4
Bus Configuration (Read/Write Setting) (2 Modules)
B30 64B0 Bus Zone 1A Source (6 items 1A to 1F) 0 to 5 --- 1 F167 0 (SRC 1)
" 64B6 Bus Zone 1A Status (6 items 1A to 1F) 0 to 4294967295 --- 1 F300 0
" 64C2 ...Repeated for Bus Zone 2
Bus Differential (Read/Write Grouped Setting) (2 or 6 Modules)
B30, B90 64E0 Bus Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 64E1 Bus Zone 1 Pickup 0.05 to 6 pu 0.001 F001 100
" 64E2 Bus Zone 1 Low Slope 15 to 100 % 1 F001 25
" 64E3 Bus Zone 1 Low Breakpoint 1 to 30 pu 0.01 F001 200
" 64E4 Bus Zone 1 High Slope 50 to 100 % 1 F001 60
" 64E5 Bus Zone 1 High Breakpoint 1 to 30 pu 0.01 F001 800
" 64E6 Bus Zone 1 High Set 0.1 to 99.99 pu 0.01 F001 1500
" 64E7 Bus Zone 1 Seal In 0 to 65.535 s 0.001 F001 400
" 64E8 Bus Zone 1 Block 0 to 4294967295 --- 1 F300 0
" 64EA Bus Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 64EB Bus Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
B90 64EC Bus Zone 1 Supervision 0 to 4294967295 --- 1 F300 1
B90 64F6 Bus Zone 1 Trip 0 to 4294967295 --- 1 F300 0
B30, B90 64F8 ...Repeated for Bus Zone 2
B90 6510 ...Repeated for Bus Zone 3
" 6528 ...Repeated for Bus Zone 4
" 6540 ...Repeated for Bus Zone 5
" 6558 ...Repeated for Bus Zone 6
Time of Day Timer (Read/Write Setting) (5 Modules)
C70 6570 Time of Day Timer 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6571 Time of Day Timer 1 Start Time 0 to 2359 --- 1 F050 0
" 6573 Time of Day Timer 1 Stop Time 0 to 2359 --- 1 F050 2359
" 6575 Time of Day Timer 1 Targets 0 to 2 --- 1 F109 0 (Self-reset)
" 6576 Time of Day Timer 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6577 ...Repeated for Time of Day Timer 2
" 657E ...Repeated for Time of Day Timer 3
" 6585 ...Repeated for Time of Day Timer 4
" 658C ...Repeated for Time of Day Timer 5
CT Trouble (Read/Write Setting) (2 or 6 Modules)
B30, B90 65A0 CT Trouble 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 65A1 CT Trouble 1 Pickup 0.02 to 2 pu 0.001 F001 100
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals